PCT401 Explosion-proof Temperature Transmitter measures the temperature of the measured medium by using the feature that the platinum resistance value varies with temperature and shows a certain functional relationship. This product adopts the high-precision thermoelectric couple and thermal resistance as the detecting elements, uses the high stability circuit for the signal processing, realizes the continuous measurement for the temperature, outputs the industrial control standard signal, and can realize the functions such as display, remote transmission etc. simultaneously. The temperature measurement part of the product adopts all stainless steel integration processing technology, and the connecting box adopts explosion-proof housing; the product has the features of strong shock resistance, quick thermal response etc.; the wire adopts the special shielded cable, with wide usage temperature range; this product is easy to install, and applicable to be used in all kinds of automatic control systems for temperature measurement.
Enquiry Now■ Accurate temperature measurement
■ Integrated structure
■ Fast response
■ Long-term stable work
■ Convenient on-site connection
■ Simple operation
■ Two-wire output 4~20mA, strong anti-interference ability;
■ Cold end temperature automatic compensation, non-linear correction circuit;
■ Mechanical transmission components are vibration-resistant and durable;
■ LCD and LED display meters are optional;
■ A variety of connection methods, which can be customized as required;
■ Support RS485 communication and HART protocol customization
|
Item |
Specification |
|||
|
Type Of Input |
RTD (PT-100/PT-200) / Thermocouple (B, E, J, K, R, S, T) |
|||
|
Pressure Range |
-50℃~250℃ |
|||
|
Output |
4~20ma@hart Protocol (16~36VDC) |
|||
|
Power Supply |
24V DC Two Wire Loop Powered |
|||
|
Accuracy |
±0.1%fs |
|||
|
Response Time |
< 200 Msec |
|||
|
Repeatability |
±0.1% |
|||
|
Display |
LCD Display |
|||
|
Surge Protection |
In-built |
|||
|
Insulation Strength |
100mω/250vdc |
|||
|
Response Time Placement Diameter: Φ12mm |
Water 0.2m/S |
Air 1m/S |
||
|
T0.5 |
T0.9 |
T0.5 |
T0.9 |
|
|
10s |
35s |
95s |
310s |
|
|
Long-term Stability |
≤0.2%FS/Year |
|||
|
Placement Diameter |
Φ12mm |
|||
|
Ambient Temperature |
20℃~70℃- |
|||
|
Humidity |
5 To 95% |
|||
|
Electrical Connection |
Die Cast Aluminum Housing |
|||
|
Protection Grade |
Ip67 |
|||
|
Maximum Mounting Torque |
25nm |
|||
|
Ex-proof Grade |
Exd IIC T6 Gb |
|||
|
Probe Material |
304 |
|||
|
Reverse Polarity |
In-built provided |
|||
|
Turn-on Time |
Less than 5 seconds |
|||
|
Power Consumption |
< 50 mW |
|||
|
Isolation |
1 kV between Input, Output & Power Supply |
|||
|
Self-Diagnosis |
Sensor open indicator |
|||
|
Sensor Options |
Input Ranges |
Recommended Min. Span |
Accuracy |
||
|
2-, 3-, 4-wire RTDs |
°C |
°F |
°C |
°F |
|
|
PT 100 |
–200 to 850 |
–392 to 1562 |
85 |
156 |
±0.1% of SPAN |
|
PT 200 |
–200 to 850 |
–392 to 1562 |
85 |
156 |
±0.1% of SPAN |
|
Thermocouples |
|||||
|
Type B |
0 to 1000 |
0 to 1832 |
100 |
183 |
±0.25% of SPAN |
|
Type E |
–270 to 1000 |
–518 to 1832 |
100 |
183 |
±0.25% of SPAN |
|
Type J |
–210 to 1200 |
–410 to 2192 |
120 |
219 |
±0.25% of SPAN |
|
Type K |
–270 to 1370 |
–518 to 2498 |
137 |
249 |
±0.25% of SPAN |
|
Type R |
–50 to 1760 |
–122 to 3200 |
176 |
320 |
±0.25% of SPAN |
|
Type S |
–50 to 1760 |
–122 to 3200 |
176 |
320 |
±0.25% of SPAN |
|
Type T |
–270 to 400 |
–518 to 752 |
40 |
75 |
±0.25% of SPAN |